SCU battery management and hybrid inverter systems

logo

SCU Battery Container

Device TypeVariantsModbus TCP (Ethernet)RS485Curtailment
BRESS 150/240
Battery container

Configuration

SCU Battery Container

In the SCU interface:

  1. Go to "Maintenance"
  2. Go to "Comm Settings"
  3. Go to "PCS"
  4. Under "BMS: Number of devices" -> Set this to the amount of batteries / BMS systems that are connected.

GRES-300-200

GRES uses the same SCU interface path, but configure based on battery rooms (up to 4 groups):

  1. Go to "Maintenance" → "Comm Settings" → "PCS"
  2. Set "BMS: Number of devices" to your battery room count (1-4 for GRES-300-200)
  3. Ensure PCS remote control is enabled for curtailment
  4. Modbus address: Default 1 (matches driver DEFAULT_BUS_ADDRESS: 1)